NEMSA INVESTIGATES ELECTRICAL ACCIDENT IN GOMBE STATE
- Preamble:
On Saturday 14th June, 2025, there were media reports of how a tragic electrical accident rocked the Tudun Wada Pantami area of Gombe State, with five persons dead and 13 others receiving treatment in hospital. The report of the incident sparked outrage and grief in the Riyel community area of the state.
The incident, which reportedly occurred in the early hours of Saturday 14th June, 2015 around 12:45 a.m., has been linked to a snapped high-tension power line that made contact with low-tension wires, leading to an uncontrolled surge of electricity sparks across the local distribution network.
Among the victims was the Permanent Secretary, Special Duties and Regional Coordination, Gombe State, Mr. Yusuf Kulani, and four others.
The incident was confirmed by the management of Jos Electricity Distribution Company Plc in a statement released by Saratu Aliyu-Dauda, the acting Head of Corporate Communications of the company. “We are deeply saddened by the unfortunate incident that occurred at approximately 00:45 hours on Saturday, affecting customers connected to the Tudun Wada Pantami Distribution Transformer two in the Riyel community. We are closely monitoring the situation, particularly in light of the palpable tension within the affected community,” JEDC said in its statement.
- Action taken by NEMSA
On getting the information, the Managing Director/Chief Executive Officer of the Nigerian Electricity Management Services Agency (NEMSA) who also doubles as the Chief Electrical Inspector of the Federation, Engr. Aliyu Tukur Tahir, FNSE, FNIPE, immediately ordered a thorough technical investigation of the tragic incident in Tudun Wada, Gombe State.
Consequently, a NEMSA technical team led by Engr. Tajudeen M. Alabi was immediately dispatched to the site on June 15, 2025, to investigate the incident in accordance with the NEMSA mandate as contained in the Electricity Act 2023.
- Preliminary Findings:
Eyewitness account and technical evaluations revealed that the incident was triggered by a structural failure of a high-tension (11kV) wooden cross-arm support, which led to the detachment of the red phase high-tension conductor. This conductor made direct contact with a low-voltage (400V) line below, causing a dangerous voltage surge into residential houses. The impact resulted in widespread electrical sparks, severe electric shocks, and the electrocution of five individuals.
Several residents sustained varying degrees of injuries while trying to disconnect their power supplies to their homes and electrical appliances including televisions, refrigerators, and meters which were extensively damaged.
The investigation uncovered several systemic and infrastructure-related issues:
- Use of aged, untreated/deteriorated wooden cross arms in the distribution network.
- Absence of standard protective devices (such as circuit breakers and RCDs) in consumer installations.
- Aged low-tension conductors, poorly maintained substations, and inadequate clearances between high-tension lines and residential structures.
- Vegetation encroachment along overhead lines.
- Failure of the protection and tripping unit at the Riyal Injection Substation, attributed to the use of non-functional battery bank which allowed the fault to persist until human intervention occurred.
From the report of the preliminary investigation, it can be said that this is an unfortunate but preventable incident had the Jos DISCO headed previous warnings from NEMSA to rectify and correct observed faults on the network. The failure of Jos utility company to carryout regular maintenance on the network as, at, and when due, led to this avoidable accident
For instance, on 30th April, this year, NEMSA in a letter Ref: NEMSA/TS/TS&IS/IFO-BAU/097/V.1, wrote to the Managing Director/Chief Executive Officer of Jos Electricity Distribution Company Plc, drawing his attention to defects observed by NEMSA officials on the networks within Gombe metropolis which are negatively impacting on the efficient delivery of service and posed great risk to safety of lives and property of electricity consumers and citizens within the network. The utility company was consequently advised to effect immediate repairs on the network to avoid ugly incident such as the one that just happened. Unfortunately, that advise was ignored by the Jos DISCO.
Electricity is associated with hazards. These hazards are real. They can even affect the personnel working in the electricity sector, so we need to use electricity safely and wisely. NEMSA hereby renew its call on utility companies to ensure regular maintenance of their networks. We equally advise Nigerians to avoid staying under power lines, erecting buildings under power lines or doing any form of business under power lines because it is very risky,
NEMSA expresses its deepest condolences to the government and people of Gombe state especially the families of the deceased on this pathetic and sad moment and assures the public of its commitment to ensuring safety in the Nigerian Electricity Supply Industry.
Meanwhile, the Agency will be working closely with the Jos Electricity Distribution Company (JEDC) and other relevant stakeholders to amongst others:
- Ensure the replacement of dilapidated infrastructure in the affected area.
- Enforce the installation of proper protective devices in residential and public buildings.
- Conduct thorough safety inspections across the distribution network.
Once more, accept our deepest condolences.
Signed
Mrs. Ama Umoren
Communications and Protocol Unit
NEMSA Headquarters, Abuja
Abuja, Saturday, 21st June, 2025